SNVT_length_f
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Length
Meters
0 .. 3.40282E38
N/A
SNVT_length_kilo
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Length
Kilometers (km)
0 .. 6,553.5
N/A
SNVT_length_micr
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Length
Micrometers, Microns
0 .. 6,553.5
N/A
SNVT_length_mil
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Length
Millimeters (mm)
0 .. 6,553.5
N/A
SNVT_lev_cont
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Continuous Level
Percent of Full Level
0 .. 100.0
N/A
SNVT_lev_cont_f
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Continuous Level
Percent of Full Scale
0 .. 100
N/A
SNVT_lev_disc
Data Length
1
Suggested Data Array Formats
Byte, Uint16, Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Discrete_levels_t
N/A
0 .. 4
255 (0xFF)(ST_NUL)
SNVT_lev_percent
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Percentage Level
Percent of Full Scale, or
Parts-per Million (ppm)
-163.840 ..
163.830
Type: 163.835 Raw:
32,767 (0x7FFF)
SNVT_lux
Data Length
1
Suggested Data Array Formats
Uint16, Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Illumination
Lux
0 .. 65,535
N/A
SNVT_magcard (only
raw data supported)
Data Length
20
Suggested Data Array Formats
Byte
SNVT_mass
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Mass
Grams
0 .. 6,553.5
N/A