5.3.13 Map Descriptor Example 9 - Multistate Output (Zone and Area Machine)
A write to the Multistate Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts. The multiple scripts are specified in the
Data Array defined under “DA_Lut_List”. The value written into the Multistate Output Data Array is used as the offset into the Data Array defined under “DA_Lut_List” to
retrieve a script number from the Data Array. Script numbers range from 0 to 65535.
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function
, Node_Name
, Data_Type
, Object_ID
, Length
, Relinquish_Default
SMD00_MO
, MultiSt_Output
, 0
, Passive
, Virtual_BCU_11
, MO
, 1
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function
, Node_Name
, Grafik_Command
, DA_Lut_List
, DA_Lut_List_Offset
, Length
, Multi_Scripts_Length
Run_scriptms_0
, MultiSt_Output
, 0
, Awt
, LUT_GRF6_0
, Run_Script_Multi
, Scr_Lst_MSO_0
, 0
, 1
, 10
The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map Descriptor per object must be defined
with a Multi_Scripts_Length value of one or greater.
The scripts per object element must be preloaded into the Data Array defined under “DA_Lut_List”: