Fieldserver Metasys N2 FS-8700-19 Manual de usuario Pagina 50

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 51
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 49
FS-8700-19_Metasys_N2 Driver Manual Page 50 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
Appendix E. Error Messages
Error Message Description and Action
MN2:#01 WARN.
Server_Hold_Timeout is
%0.3fs
For N2Open Slave
typical value is %0.3fs
Typically N2open Clients are configured to timeout after 200ms. If a
FieldServer is configured as a Server the Server_Hold_Timeout time
should be set to 0.175s or less otherwise the response will be suppressed.
This message is printed if the Server_Hold_Timeout is set for >0.175s.
If the Client’s timeout is >200ms this message may be ignored.
Vista de pagina 49
1 2 ... 45 46 47 48 49 50 51

Comentarios a estos manuales

Sin comentarios