FS-8700-130 Notifier NCA2/NFS-3030 Manual Page 10 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com
5.4 Client Side Map Descriptor Parameters
5.4.1 FieldServer Related Map Descriptor Parameters
Name of this Map Descriptor
Up to 32 alphanumeric characters
Name of Data Array where data is to be
stored in the FieldServer
One of the Data Array names from
Section 4
Starting location in Data Array
0 to (Data_Array_Length-1) as specified
in Section 4.
Function of Map Descriptor
5.4.2 Driver Related Map Descriptor Parameters
Name of Node to fetch data from
One of the Node names
specified in Section 5.3
Detector
Module
Detector_Trouble
Module_Trouble
Panel
Panel_Trouble
Bell_Trouble
Node_Trouble
Starting address of block
As per Data_type
Detector
Module
1-1749
Detector_Trouble
Module_Trouble
1-159 for point troubles
Panel
1-1056 for Panel circuits
Panel_Trouble
1-96 for Panel troubles
Bell_Trouble
1-4 for Bell circuits
Node_Trouble
1-509 for Node troubles
Specify Loop number. To capture system level events
specify it as 0 or omit this parameter
Specify whether driver should clear Node(s) memory area
upon receipt of “SYSTEM RESET” message from Panel.
Specify whether driver should clear Node(s) memory area
upon receipt of “SYSTEM NORMAL” message from Panel.