FS-8700-42_Spectronics Driver Manual Page 14 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: suppo[email protected]
Appendix A.4. Connection to York Modbus Microgateway
If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the
Microgateway is defined by the address DIP switches. If switch 4 is set to ‘On’ and the other
switches are set to ‘off’ then Node_ID of the Microgateway is ‘247’, the parity is ‘Even’, and
the stop bits are 1. Other Node_ID combinations can be found in the York Modbus
Microgateway Installation Manual.