FS-8700-112 Gamewell-FCI 7100 Driver Manual Page 13 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Appendix A. Useful Features
Appendix A.1. Extending the Event Table
New event causes may be added to the Event Table (Refer to Appendix C.1) and the index value or category of
existing event causes modified by adding a section to the configuration CSV file. The examples below illustrate
this:
Appendix A.1.1. Map Descriptor Parameters
Name (Description) of the new Event Types
Any string – max 19
characters
Provide the value that should be stored for a specific
event.
Specify the category to which the new event should
belong
Appendix A.1.2. Example 1: Index value of 'Trouble' is updated to a new value of 100
Appendix A.1.3. Example 2: New Entry is added
Since it has been added as category=3, only Map Descriptors with 'Event Type' set to Alarm or ANY will capture
messages with this event description
For categories use the following values
'Other' = 1
'Fault' = 2
'Alarm' = 3
'Trouble' = 4
Appendix A.2. Panel Synchronization
Manual synchronization is required. Push the reset button on the panel. This transmits a reset message to the
FieldServer, which clears the data in the FieldServer. After a reset the panel sends messages to report all abnormal
states. When all these messages have been processed the FieldServer and panel will be synchronized. This
process can be repeated at any time.